Technical Attributes |
Brand |
CLICK |
Item |
PLC |
Series |
Ethernet Analog |
Ladder Memory |
8k steps |
User Data Memory |
16 KB |
Programming Language |
Ladder |
Programming Software |
CLICK programming software v2.20 or later and CLICK CPU firmware v2.20 or later |
Communication Port and Connection Type(s) |
- (1) Ethernet 10/100Base-T (RJ45)
- (1) RS-232 (RJ12)
- (1) RS-485 (3-pin terminal)
|
Port Protocol(s) |
- Modbus TCP Client/Server
- Modbus RTU Master/Slave
- ASCII In/out
- EtherNet/IP explicit messaging adapter
- EtherNet/IP implicit messaging adapter
- programming and monitoring
|
Port Speed(s) |
- 10/100 Mbps
- up to 115.2k baud
|
Real Time Clock/Calendar |
Yes |
Retentive Memory |
Yes |
Battery Backup |
Yes |
Maximum Expansion Modules Allowed |
8 |
External Power Requirement |
24 VDC |
Number of Discrete Input Points |
4 |
Nominal Input Voltage |
120 VAC |
Voltage Type |
AC |
Number of Isolated Discrete Input Commons |
1 |
Number of Points per Discrete Input Common |
4 |
Number of Discrete Output Points |
4 |
Nominal Output Voltage |
6-240 VAC/6-27 VDC |
Discrete Output Type |
Relay |
Relay Configuration |
(4) Form A (SPST) relays |
Load Current |
1A/point |
Number of Isolated Discrete Output Commons |
1 |
Number of Points per Discrete Output Common |
4 |
Number of Analog Input Channels |
4 |
Analog Input Signal Type |
Current |
Number of Non-Isolated Analog Input Commons |
1 |
Number of Points per Analog Input Common |
4 |
Input Resolution |
12-bit |
Input Current Signal Range |
0-20 mA |
Number of Analog Output Channels |
2 |
Analog Output Signal Type |
Current |
Number of Non-Isolated Analog Output Commons |
1 |
Number of Points per Analog Output Common |
2 |
Output Resolution |
12-bit |
Output Current Signal Range |
4-20 mA |
Maximum Number of PID Loops |
8 |
Includes |
Removable terminal block |
Additional Information |
Purchase D2-BAT-1 backup battery separately |